Ethernet RJ45

The C6015 has two Gigabit LAN ports (X102, X103). The 100Base-T, 1000Base-T, and 2500Base-T Ethernet standards enable the connection of corresponding network components and data rates of 100/1000/2500 Mbit/s. The required speed is selected automatically.

The RJ45 connection technology with twisted-pair cables is used. The maximum length of the cable connection is 100 m.

The controllers are used as follows, based on the device generation:

Controller classification based on device generation

Device generation

Controller

Mbit/s

C6015-0010

Intel® i210 for LAN1 and LAN2

100/1000

C6015-0020

Intel® i210 for LAN1 and LAN2

100/1000

C6015-0030

Intel® i226 for LAN1 and LAN2

100/1000/2500

The Ethernet ports i210/i226 connected via PCIe® are suitable for cycle times <= 1 ms and for distributed clock applications with EtherCAT.

Ethernet RJ45 1:
Fig.3: Ethernet interface pin numbering
Ethernet interface pin assignment

Pin

Signal

Description

1

T2 +

Pair 2

2

T2 -

3

T3 +

Pair 3

4

T1 +

Pair 1

5

T1 -

6

T3 -

Pair 3

7

T4 +

Pair 4

8

T4 -

The LEDs of the LAN interfaces indicate the activity and the data transmission rate (Mbit/s). The LED (LINK/ACT) highlighted completely green in the figure indicates whether the interface is connected to a network. If this is the case, the LED lights up green. The LED flashes green when data transmission is in progress on the interface.

The green/orange LED (SPEED) shown in the figure indicates the data transmission rate.

The device generations differ in terms of the possible data transmission rate. The following tables show what the LEDs mean with regard to the potential data transmission rate.

LED meaning: speed 100/1000 Mbit/s

Mbit/s

LED

100

Lights up orange

1000

Lights up green

LED meaning: speed 100/1000/2500 Mbit/s

Mbit/s

LED

100

Off

1000

Lights up orange

2500

Lights up green