Technical data - BX
Technical data | BX3100 | BX5100 | BX5200 | BX8000 | BX9000 |
|---|---|---|---|---|---|
Processor | 16 bit micro-controller | ||||
Diagnostic LEDs | 2 x power supply, 2 x K-Bus | ||||
Display | FSTN 2 x 16 lines display for diagnosis or own texts, illuminated | ||||
Switch | Joystick switch for parameterization and diagnosis | ||||
Clock | battery-powered internal clock for time and date | ||||
Configuration and programming software | TwinCAT PLC | ||||
Fieldbus interface | PROFIBUS DP | CANopen | DeviceNet | - | Ethernet |
Fieldbus connection | D-sub, 9-pin | Open style connector, 5 pin | - | RJ45 | |
SSB | CANopen-based sub-bus interface | ||||
Terminal Bus (K-Bus) | 64 (255 with K-bus extension) | ||||
Digital peripheral signals | 2040 inputs/outputs | ||||
Analog peripheral signals | 1024 inputs/outputs | ||||
Configuration possibility | via TwinCAT or the controller | ||||
max. number of bytes, fieldbus | depending on fieldbus | ||||
max. number of bytes, PLC | 2048 bytes of input data, 2048 bytes of output data | ||||
Supply | BX3100 | BX5100 | BX5200 | BX8000 | BX9000 |
|---|---|---|---|---|---|
Power supply (Us) | 24 VDC (-15% /+20%) | ||||
Input current (Us) | 180 mA + (total K-bus current)/4, see UL requirements | ||||
Starting current (Us) | approx. 2.5 x continuous current | ||||
K-bus current (5 V) | maximum 1450 mA | ||||
Power contact voltage (Up) | 24 VDC max. | ||||
Power contact current load (Up) | max. 10 A, see UL requirements | ||||
Dielectric strength | 500 V (power contact/supply voltage/Ethernet/fieldbus) | ||||
| ||
![]() | UL requirements For power supplies of the BX Controller (Us) und the Power Contacts (Up) use a 4 A fuse or an NEC Class 2-compliant power supply to meet the UL requirements! | |
Technical data | BX3100 | BX5100 | BX5200 | BX8000 | BX9000 |
|---|---|---|---|---|---|
Permissible ambient temperature range during operation | 0°C ... +55 °C (bevore hardware version 4.4) | 0°C ... +55 °C | |||
Permissible ambient temperature range during storage | -20°C ... +85 °C (bevore hardware version 4.4) | -20°C ... +85 °C | |||
Relative humidity | 95 % no condensation | ||||
Vibration / shock resistance | conforms to EN 60068-2-6 / EN 60068-2-27 | ||||
EMC immunity / emission | conforms to EN 61000-6-2 / EN 61000-6-4 | ||||
Protection class | IP20 | ||||
Approvals/markings* | CE, UKCA, cULus, EAC | ||||
*) Real applicable approvals/markings see type plate on the side (product marking).
Mechanical data | BX3100 | BX5100 | BX5200 | BX8000 | BX9000 |
|---|---|---|---|---|---|
Weight | app. 170 g | ||||
Dimensions (W x H x D) | app. 83 mm x 100 mm x 90 mm (BX8000: app. 65 mm x 100 mm x 90 mm) | ||||
Mounting | with latch, on mounting rail (35 mm DIN rail) | ||||
Installation position | any | ||||
Connection cross-section | 0.08 mm² ... 2.5 mm² | ||||