Technical data - BX
Technical data  | BX3100  | BX5100  | BX5200  | BX8000  | BX9000  | 
|---|---|---|---|---|---|
Processor  | 16 bit micro-controller  | ||||
Diagnostic LEDs  | 2 x power supply, 2 x K-Bus  | ||||
Display  | FSTN 2 x 16 lines display for diagnosis or own texts, illuminated  | ||||
Switch  | Joystick switch for parameterization and diagnosis  | ||||
Clock  | battery-powered internal clock for time and date  | ||||
Configuration and programming software  | TwinCAT PLC  | ||||
Fieldbus interface  | PROFIBUS DP  | CANopen  | DeviceNet  | -  | Ethernet  | 
Fieldbus connection  | D-sub, 9-pin  | Open style connector, 5 pin  | -  | RJ45  | |
SSB  | CANopen-based sub-bus interface  | ||||
Terminal Bus (K-Bus)  | 64 (255 with K-bus extension)  | ||||
Digital peripheral signals  | 2040 inputs/outputs  | ||||
Analog peripheral signals  | 1024 inputs/outputs  | ||||
Configuration possibility  | via TwinCAT or the controller  | ||||
max. number of bytes, fieldbus  | depending on fieldbus  | ||||
max. number of bytes, PLC  | 2048 bytes of input data, 2048 bytes of output data  | ||||
Supply  | BX3100  | BX5100  | BX5200  | BX8000  | BX9000  | 
|---|---|---|---|---|---|
Power supply (Us)  | 24 VDC (-15% /+20%)  | ||||
Input current (Us)  | 180 mA + (total K-bus current)/4, see UL requirements  | ||||
Starting current (Us)  | approx. 2.5 x continuous current  | ||||
K-bus current (5 V)  | maximum 1450 mA  | ||||
Power contact voltage (Up)  | 24 VDC max.  | ||||
Power contact current load (Up)  | max. 10 A, see UL requirements  | ||||
Dielectric strength  | 500 V (power contact/supply voltage/Ethernet/fieldbus)  | ||||
  | ||
![]()  | UL requirements For power supplies of the BX Controller (Us) und the Power Contacts (Up) use a 4 A fuse or an NEC Class 2-compliant power supply to meet the UL requirements!  | |
Technical data  | BX3100  | BX5100  | BX5200  | BX8000  | BX9000  | 
|---|---|---|---|---|---|
Permissible ambient temperature range during operation  |    0°C ... +55 °C (bevore hardware version 4.4)  | 0°C ... +55 °C  | |||
Permissible ambient temperature range during storage  | -20°C ... +85 °C (bevore hardware version 4.4)  | -20°C ... +85 °C  | |||
Relative humidity  | 95 % no condensation  | ||||
Vibration / shock resistance  | conforms to EN 60068-2-6 / EN 60068-2-27  | ||||
EMC immunity / emission  | conforms to EN 61000-6-2 / EN 61000-6-4  | ||||
Protection class  | IP20  | ||||
Approvals/markings*  | CE, UKCA, cULus, EAC  | ||||
*) Real applicable approvals/markings see type plate on the side (product marking).
Mechanical data  | BX3100  | BX5100  | BX5200  | BX8000  | BX9000  | 
|---|---|---|---|---|---|
Weight  | app. 170 g  | ||||
Dimensions (W x H x D)  | app. 83 mm x 100 mm x 90 mm (BX8000: app. 65 mm x 100 mm x 90 mm)  | ||||
Mounting  | with latch, on mounting rail (35 mm DIN rail)  | ||||
Installation position  | any  | ||||
Connection cross-section  | 0.08 mm² ... 2.5 mm²  | ||||