X02: DC link

X02: DC link 1:

DC link AX5000 (60 A…170 A devices)!

When establishing a DC link network (only for 60 A…170 A devices!), it is essential to follow the chapter:
“Connection example – DC link network (60 A…170 A devices)”.

DANGER

Serious risk of injury due to high electrical voltage!

Due to the DC link capacitors, the DC link terminal points
“DC+ and DC-” and “RB+ and RB-” may be subject to life-threatening voltages exceeding 875 VDC, even after the servo drive was disconnected from the supply network.
After disconnection, wait for 15 minutes (AX5160/AX5172), 30 minutes (AX5190/AX5191) or 45 minutes (AX5192/AX5193) and measure the voltage at the DC link terminal points DC+ and DC-. Safe working is possible once the voltage has fallen below 50 V.

AX5160 – AX5172

X02: DC link 2:

Terminal point

Connection

Tightening torque of the terminal points

DC +

DC link +



2.5 Nm…4.5 Nm

DC -

DC link -

AX5190 – AX5191

X02: DC link 3:

Terminal point

Connection

Tightening torque of the terminal points

DC +

DC link +



6 Nm…8 Nm

DC -

DC link -

AX5192 – AX5193

X02: DC link 4:

Terminal point

Connection

Tightening torque of the terminal points

DC +

DC link +



25 Nm…30 Nm

DC -

DC link -