EXTLATCH

ASCII - Command

EXTLATCH

 

 

Syntax Transmit

EXTLATCH [Data]

 

Syntax Receive

EXTLATCH <Data>

Available in

 

Type

Variable rw

MMI

No

ASCII Format

Integer8

CANBus Object Number

3681 (hex)

DIM

-

PROFIBUS PNU

1985 (dec) IND = 0000xxxx (bin)

Range

0 .. 2

DPR

385 (dec)

Default

0

 

Opmode

All

Data Type Bus/DPR

Integer8

Drive State

Disabled + Reset (Coldstart)

Weightning

 

Start Firmware

4.61

 

Configuration

Yes

Revision

1.5

Function Group

Position Controller

EEPROM

Yes

Short Description

Selection of the Source of the Latch Inputs

Description

The configuration variable EXTLATCH defines the source for the position information using the Latch functions of the digital inputs (IN1MODE =26 and/or IN2MODE =26). If more than one inputs (1 or 2) are configured as Latch input, EXTLATCH defines thedifferent sources. If only one input is configured as Latch input, both different sources are stored at the same time.

Status

Latch with Input 1

Latch with Input 2

EXTLATCH=0

Resolver/EnDAT/Hiperface depends on FBTYPE

Resolver/EnDAT/Hiperface depends on FBTYPE

EXTLATCH=1

external encoder

Resolver/EnDAT/Hiperface depends on FBTYPE

EXTLATCH=2

external encoder

external encoder