Data for operation and environment

Notice

Shorter service life due to high temperatures

Temperatures above 40°C and encapsulated installation can shorten the service life of the product.

  • Operate the distributed servo drive systems only under the operating and environmental conditions specified in this chapter

Beckhoff products are designed for operation under certain environmental conditions, which vary according to the product. The following specifications must be observed for operation and environment in order to achieve the optimum service life for the products.

Environmental requirements

Ambient temperature during operation

0 °C to +40 °C

Ambient temperature during transport

-25 °C to +70 °C, maximum fluctuation 20 K per hour

Ambient temperature during storage

-25 °C to +55 °C, maximum fluctuation 20 K per hour

Power derating

No power derating up to 1000 m above sea level

Power derating of 1% / 100 m from 1000 m up to a maximum of 2000 m above sea level

Installation altitude

max. 2000 m

Permissible humidity in operation

95% relative humidity, no condensation

Permissible humidity during transport and storage

15% to 95% relative humidity, no condensation

Corrosion protection

Not required:

Special measures are to be taken in consultation with the vendor if the environmental conditions are extreme or if they differ from those described in this chapter.

Degree of pollution

2 for AX883x
3 for AMP8620, AMP8805, AMP80xx, AMP85xx

Specifications for intended use

Cooling

Convection

Insulation material class

F according to IEC 60085 and UL1446 class F

Protection rating

Housing: IP65
Shaft feedthrough: IP54 / IP20 in mounting position V3
Shaft feedthrough with shaft sealing ring: IP65

Vibration resistance

5 g, 150 Hz according to EN 60068-2-6

Shock resistance

25 g, 30 ms according to EN 60068-2-27

EMC requirements

conforms to EN 61800-3

Approvals

CE
EAC
cURus
See chapter: Guidelines and Standards