Data for operation and environment

Notice

Shorter service life due to high temperatures

Temperatures above 45 °C and encapsulated installation can shorten the service life of the product.

  • Operate the only under the operating and environmental conditions specified in this chapter

Notice

Damage caused by conductive dusts

Penetration or deposition of conductive dust can lead to short circuits, malfunctions, fire or explosion hazards.

  • Do not use in environments with conductive dusts

Beckhoff products are designed for operation under certain environmental conditions, which vary according to the product. The following specifications must be observed for operation and environment in order to achieve the optimum service life of the products.

Environmental requirements

Ambient temperature during operation

  • Convection-cooled devices (up to 0.75 kW)
    0 °C to +40 °C
    Extended temperature range up to +50 °C with a power reduction of 2 %/K
  • Devices with built-in fans (0.75 kW and above)
    0 °C to +45 °C
    Extended temperature range up to +55 °C with a power reduction of 2 % per Kelvin

Ambient temperature during transport

-25 °C to +70 °C, maximum fluctuation 20 K per hour

Ambient temperature during storage

-25 °C to +55 °C, maximum fluctuation 20 K per hour

Power derating

No power derating up to 1000 m above sea level
Power derating of 1 %/100 m from 1000 m up to a maximum of 3000 m above sea level

Installation altitude

A reduction of the overvoltage category is necessary from an installation altitude of 2000 m up to a maximum of 3000 m above sea level. Observe the derating.

Permissible humidity during operation

5 % to 95 % relative humidity, no condensation

Permissible humidity during transport and storage

5 % to 95 % relative humidity, no condensation

Corrosion protection

Not required:
Special measures are to be taken in consultation with the vendor if the environmental conditions are extreme or if they differ from those described in this chapter.

Pollution degree

2 according to EN 60204 and EN 50178

Overvoltage category

3 according to EN 61800-5-1

Ventilation

  • Free convection
  • Integrated and temperature-controlled fan

Insulation material class

F according to IEC 60085 and UL1446 class F

Protection rating

Devices IP20
Terminals IP20

Installation position

Vertical

Vibration resistance

1 g, 150 Hz according to EN 60068-2-6

Shock resistance

5 g, 30 ms according to EN 60068-2-27

EMC requirements

Conforms to EN 61800-3

Approvals

CE

See chapter Guidelines and Standards