AC input

AC input

AC input

Nom.

AC 100-240V

Suitable for TN, TT and IT networks with alternating voltage

AC input range

Min.

90-264Vac

Continuous operation

Min.

264-300Vac

For up to 500 ms max.

Permissible voltage L or N to earth

Max.

300Vac

Continuous according to IEC 62477-1

Input frequency

Nom.

50-60Hz

±6%

Turn-on voltage

typ.

81Vac

Static, see Fig. Input voltage range

Shut-down voltage

typ.

63Vac/71Vac

At zero load / nominal load, static value, see Fig. Input voltage range

External input protection

See recommendations in chapter External input protection

AC input

 

AC100V

AC120V

AC230V

 

Input current

typ.

2.60A

2.17A

1.18A

At 24V, 10A, see Fig. Input current over output current

Power factor 1)

typ.

0.99

0.98

0.93

At 24V, 10A, see Fig. Power factor over output current

Crest factor 2)

typ.

1.6

1.7

2.0

At 24V, 10A

Start-up delay

typ.

360ms

260ms

200ms

See Fig. Switch-on behavior definitions

Rise time

typ.

60ms

60ms

60ms

At 24V, 10A constant current load, 0mF load capacity, see Fig. Switch-on behavior definitions

typ.

230ms

230ms

230ms

At 24V, 10A constant current load, 10mF load capacity, see Fig. Switch-on behavior definitions

Turn-on overshoot

Max.

200 mV

200 mV

200 mV

See Fig. Switch-on behavior definitions

1) The power factor is the ratio of real (or active) power to apparent power in an AC circuit.
2) The crest factor is the mathematical ratio of the peak value over the RMS value of the input current waveform.

AC input 1:
Input voltage range; switch-on behavior definitions
AC input 2:
Input current over output current; power factor over output current