External input protection
The device is tested and approved for circuits that are fused up to 30A (UL) and 32A (IEC). External protection is only required if the supply line has a protection that is higher than this.
Also check the local regulations and requirements. Local regulations may apply in some countries.
If an external fuse is required or used, minimum requirements must be taken into account to avoid false tripping of the circuit breaker. A circuit breaker with a minimum value of 10A with B characteristic or 6A with C characteristic should be used.