Introduction
2-channel analog input + 2-channel analog output, parameterizable, 16-bit
The EP43x4-1002 EtherCAT Box modules have two analog inputs, two analog outputs and two digital inputs. The analog inputs and outputs can be parameterized individually. The following measuring ranges and output ranges are available:
- EP4304-1002: ±10 V
- EP4314-1002: ±10 mA or ±20 mA
The resolution of the measuring signals and output signals is 16 bit. The two output channels have a common ground potential with the supply voltage 24 VDC UP.
A digital type 3 input with 10 µs input filter time and an analog input and an analog output are arranged on one M12 socket each. Since the digital input as well as the analog inputs and outputs are arranged together on one M12 socket each, complex end devices can be controlled with one connection cable. This saves additional costs, cable channels and installation work.
![]() | Misinterpretation of the measured values possible In the factory setting the "Extended Range" mode is enabled. In "Extended Range" mode the measuring range is slightly larger than the nominal measuring range. The value 0x7FFF corresponds to approximately 107% of the full scale value.
|