EP2339-0121 - Technical data

All values are typical values over the entire temperature range, unless stated otherwise.

EtherCAT

Connection

2 x M8 socket, 4-pin, A-coded, shielded

Electrical isolation

500 V

Supply voltages

Connection

Input: M8 connector, 4-pin, A-coded

Downstream connection: M8 socket, 4-pin, A-coded

US nominal voltage

24 VDC (-15 % / +20 %)

US sum current: IS,sum

max. 4 A

Current consumption from US

60 mA

Rated voltage UP

24 VDC (-15 % / +20 %)

UP sum current: IP,sum

max. 4 A

Current consumption from UP

50 mA

+ sensor supply

Digital inputs

Number

0 to 16

Each digital input can alternatively be used as a digital output.

Connection

16 x M8 socket

Cable length

max. 30 m

Input filter

3.0 ms

Characteristics

Ground switching

Signal voltage "0"

18…30 V

Signal voltage "1"

0…7 V

Sensor power supply

24 VDC from UP.

max. 0.5 A in total, short-circuit proof.

Digital outputs

Number

0 to 16

Each digital output can alternatively be used as a digital input.

Connection

16 x M8 socket

Cable length

max. 30 m

Characteristics

Ground switching

Load current

max. 0.5 A

Changeover times

TON: 60 µs typ., TOFF: 300 µs typ.

Housing data

Dimensions W x H x D

60 mm x 126 mm x 26.5 mm (without plug connectors)

Weight

approx. 260 g

Installation position

variable

Material

PA6 (polyamide)

Environmental conditions

Ambient temperature during operation

-25 … +60 °C
-25 … +55 °C according to cURus

Ambient temperature during storage

-40 … +85 °C

Vibration resistance, shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27
Additional tests

EMC immunity / emission

conforms to EN 61000-6-2 / EN 61000-6-4

Protection class

IP65, IP66, IP67 (conforms to EN 60529)

Approvals/markings

Approvals/markings *)

CE, cURus

*) Real applicable approvals/markings see type plate on the side (product marking).