S-0-0134 Master control word

The parameter contains the master control word. This parameter is cyclically transferred in each communication cycle from the controller to the drive. It contains the set operating mode (bits 8, 9, 11), Halt Drive (bit 13) and controller enable (bit 14).

Attributes

Name

Value

Datatype

binary

Data length in bit

16

Decimal point

0

Min value

-

Default

0.0

Max value

-

Unit

-

Changeable in EtherCAT state

No

Cyclic transfer

MDT

Device parameter

No

Related to interface revision

No

The controller selects the operation mode via the 3 "operation mode" bits 8, 9, 11 of S-0-0134. If operating mode 0 is selected here, the drive activates the operating mode selected in the IDN "PrimaryOperationMode" S-0-0032. If 1 is sent by the controller, the "first secondary mode" is activated, see S-0-0033.

Bit pattern:

Bit

Meaning

0 -5

Reserved

6

Real time control bit 1
Real time control bit 1

7

Real time control bit 2
Real time control bit 2

8-9

Operation mode low
Operation mode low
0 = mode 0 or 4, depending on bit 11
1 = mode 1 or 5, depending on bit 11
2 = mode 2 or 6, depending on bit 11
3 = mode 3 or 7, depending on bit 11

10

Control unit synchronisation bit
Control unit synchronisation bit IPOSYNC toggles with cycle time tNcyc and is used to synchronise the interpolation.

11

Operation mode high
Operation mode high
0 = mode 0 to 3
1 = mode 4 to 7

12

Reserved

13

 

Halt/ restart drive
Halt Drive/ Restart Drive
0 = Halt Drive
1 = Restart Drive

14

Enable drive
Enable drive
0 = Drive not enabled
1 = enable Drive

15

Drive On/Off
Drive On/Off
0 = drive off:
When changing from 1 to 0: the maximum drive off delay time (IDN S-0-0273) is started, drive is decelerated as best as possible according to the emergency stop deceleration (IDN S-0-0429), followed by disabling of the torque/force at n min, after the drive off delay time (IDN S-0-0207). The power stage can remain in an activated state (only possible when bit 14=1). After the maximum drive off delay time (IDN S-0-0273) is elapsed, the locking of brake is initiated and the torque/force is disabled.
1 = drive on:
When changing from 0 to 1: drive follows the command values of the control unit after the drive on delay time (IDN S-0-0206).

S-0-0134 Master control word 1:

For further information please look into the involved IDN:

S-0-0099