Teaching
![]() | Note the revision number on the module Teaching is only required for modules with a revision level less than or equal to 17. For more information, refer to the chapter "Name plate" in the XTS Standard original operating instructions. |
![]() | Change teaching file number Always change the number of the teaching file before commencing with a new teaching. The old file will be used and overwritten if the number of the teaching file is not changed or if the configuration is not loaded. Beckhoff recommends using the current date for the number of the teaching file. For the first teaching on April 3rd, 2021, for example, the numbers 202104031 could be used and for the second teaching on the same day the numbers 202104032 and so on. |
- ►Expand Teaching
- ►Activate the checkbox Is Teaching Enabled to display the input field Teaching File Number
OR
- ►Deactivate the checkbox Is Teaching Enabled to hide the input field Teaching File Number
- ►Enter a number in the input field Teaching File Number
Further information can be found in chapter Teaching function.