Adjusting the cycle time of the XTS task
![]() | The cycle time of the new XTS task must be set to 250 µs. |
- ►Expand Solution Explorer > TwinCAT Project > SYSTEM
- ►Double-click on Real-Time
- ►In the project window click on the Settings tab
- ►Ensure that the XTS task is running on the correct RT-Core
- ►If required, change RT-Core via the drop-down menu
- ►Ensure that the Base Time is set to 250 µs
- ►If required, set Base Time value to 250 µs via the drop-down menu
- ►Expand Solution Explorer > TwinCAT Project > SYSTEM > Tasks
- ►Double-click on the new XTS Task
- ►In the project window click on the Task tab
- ►Enter the value 1 in the input field Cycle ticks or set it using the arrow keys
![]() | For more information on the required Real Time settings, please refer to the relevant documentation or contact the product specialist responsible for your region. |