Parameter (Init)

Parameter (Init) 1:
►Click the Parameter (Init) tab in the project window
►Expand MoverIdDetection
Parameter (Init) 2:
►If necessary, reduce the value for the minimum position change during Mover ID detection in the input field DetectionMinMovement to reduce the position change of the movers

OR

►If necessary, increase the value for the minimum position change during Mover ID detection in the input field DetectionMinMovement to increase the position change of the movers
Parameter (Init) 3:
►If necessary, reduce the value for the current change filter in the input field DetectionFilter to build up the current more slowly and make Mover ID detection smoother

OR

►If necessary, increase the value for the current change filter in the input field DetectionFilter to build up the current more quickly and make Mover ID detection more jerkily
Parameter (Init) 4:
►If necessary, change the DetectionCurrentRamp value for the ramp of the Mover ID detection current
Parameter (Init) 5:
►If necessary, change the DetectionMaxCurrent value for the limit of the Mover ID detection current