Error

ID

Message

Cause

Number of the solution

10000

Interpolator Object is missing

Damaged TcSoftDrive configuration within the TwinCAT configuration

1

 

 

 

 

 

 

 

 

 

 

 

 

10000

PositionCtrl Object is missing

Damaged TcSoftDrive configuration within the TwinCAT configuration

1

 

 

 

 

 

 

 

 

 

 

 

 

10000

VelocityCtrl Object is missing

Damaged TcSoftDrive configuration within the TwinCAT configuration

1

 

 

 

 

 

 

 

 

 

 

 

 

10000

Encoder Object is missing

Damaged TcSoftDrive configuration within the TwinCAT configuration

1

 

 

 

 

 

 

 

 

 

 

 

 

10000

Filter Object is missing

Damaged TcSoftDrive configuration within the TwinCAT configuration

1

 

 

 

 

 

 

 

 

 

 

 

 

10000

Feedforward Object is missing

Damaged TcSoftDrive configuration within the TwinCAT configuration

1

 

 

 

 

 

 

 

 

 

 

 

 

10001

Velocity difference too big for emergency ramp down

Triggering of an emergency ramp by TcSoftDrive

Difference between the setpoint and actual value of the velocity is more than 250 mm/s

 

2

3

 

 

 

 

 

 

 

 

 

 

10001

Emergency ramp takes too long

Emergency ramp triggered by TcSoftDrive requires more time than the time of 0.5 sec configured in the parameter "EmergencyRamp"

 

 

 

4

5

 

 

 

 

 

 

 

 

10002

Velocity following error - check setpoint generation & commutation (actual velocity != command velocity)

Different sign to the setpoint velocity and actual velocity, deviation from one another by more than the velocity of 1000 mm/s set in the parameter "CommutationErrorVelocity"

 

 

 

 

 

6

7

8

9

 

 

 

 

10003

New mover re-sort while axis is enabled

New mover search activated during the enabling of the axis by the NC controller

 

2

 

 

 

 

 

 

 

 

 

 

 

10004

New Mover 1 detection while axis is enabled

New Mover 1 detection started during the enabling of the axis by the NC controller

 

2

 

 

 

 

 

 

 

 

 

 

 

10005

HW error occur after Mover 1 detection is started

HW error during running Mover 1 detection

 

 

 

 

 

 

 

 

 

10

 

 

 

10006

Both movements while Mover 1 detection do not fit together

Each mover performs two small movements during the Mover 1 detection:

These movements must take place in different directions

 

 

 

 

 

 

 

 

 

 

11

12

 

10007

Time out while Mover 1 detection is running

No ending of the Mover 1 detection possible within the specified time

 

 

 

 

 

 

 

 

 

 

 

 

13