Error

ID

Message

Cause

Number of the solution

9000

Xts task cannot be accessed. Is the context of the TcIoXts driver set correctly?

Context setting in the "TcIoXtsDrv" object incorrect

 

 

 

12

 

 

 

 

 

 

 

 

 

 

9001

Cycle time "x" µs of XTS task is not supported! Set cycle time to 250 µs.

Cycle time of the XTS task is not equal to 250 µs:
A cycle time of 375 µs is also possible, but leads to losses of performance and dynamics

1

 

 

 

 

 

 

 

 

 

 

 

 

 

9002

A XTS mover is lost at "y" mm. Please restart TwinCAT to perform a new detection.

Position "y" is at the transition from a motor module to a power supply module:
Incorrect order of the power supply modules when configuring the XTS or no reaction or defect of the motor module at position "y"

 

 

8

 

 

 

 

 

 

 

 

 

 

 

9003

The motor module "x" with name "y" has an error

Error on motor module "x"

 

 

 

 

13

 

 

 

 

 

 

 

 

 

9004

Out of memory. XTS mover count is not supported.

Number of movers in use not supported

 

 

 

 

 

14

 

 

 

 

 

 

 

 

9005

TcIoXts driver has failed to start up. Please check the configuration and bootdata files!

Driver cannot start

 

 

 

 

 

 

15

 

 

 

 

 

 

 

9006

Teaching file is invalid.

The stored teaching file does not match the XTS system

Teaching file originates from a different system

 

 

 

 

 

 

 

16

 

 

 

 

 

 

9007

Teaching data file "y" is corrupt

The teaching file in the directory "C:\TwinCAT\3.1\Target\Config\TcIoXts" is corrupt or missing

 

4

 

 

 

 

 

 

 

 

 

 

 

 

9008

Teaching file of XTS module "x" is invalid

Damaged or missing teaching file in the directory:

"C:\TwinCAT\3.1\Target\Config\TcIoXts"

Or motor module "x" not correctly taught

 

4

 

 

 

 

 

 

 

 

 

 

 

 

9009

Saving of teaching file "Bezeichnungsstring" ("Designation string") has failed

The teaching file "Bezeichnungsstring" ("Designation string") could not be saved on the system

 

 

 

 

 

 

 

 

17

 

 

 

 

 

9010

Mover "x" is frozen at position "y" mm

EtherCAT connection interrupted, position "y" is at the transition from a motor module to a power supply module

Incorrectly order of power supply modules when configuring the XTS

 

 

8

 

 

 

 

 

 

 

 

 

 

 

9011

„…" cannot be loaded. Please check that the installation is correct

Driver cannot start

 

 

 

 

 

 

15

 

 

 

 

 

 

 

9012

Mover1 cannot be detected. A general error occurs on mover "x" during the detection process.

Mover 1 detection faulty, no mover 1 identified

 

 

 

 

 

 

 

 

 

18

 

 

 

 

9013

The SoftDrive "x" is not responding. Please check the axis configuration or the SoftDrive version.

SoftDrive incorrectly linked or no suitable version of the SoftDrive driver for the TwinCAT configuration

 

 

 

 

 

 

 

 

 

 

19

 

 

 

ID

Message

Cause

Number of the solution

9014

No Mover1 has been detected! Check if there is a "Mover1" on the system and restart the detection.

No mover with Mover 1 magnetic plate set on the system

 

 

 

 

 

 

 

 

 

 

 

20

 

 

9015

Too many Mover1's have been detected! Make sure that there is only one mover with Mover 1 magnet plate set on the System

More than one mover with Mover 1 magnetic plate set on the system

 

 

 

 

 

 

 

 

 

 

 

20

 

 

9016

The Axis "x" gets an enable command before "Mover1" has been detected. If there's no Mover1 on the XTS set 'MoverIdDetectionMode' to 'Standard'

Controller enable for a mover before mover 1 was found

 

 

 

 

 

 

 

 

 

 

 

 

21

 

9017

MoverIdDetection was interrupted by changing the 'MoverIdDetectionMode'

Change of the 'MoverIdDetectionMode' while MoverID detection is running

 

 

 

 

 

 

 

 

 

 

 

 

 

22