Defining exceptions
Exceptions for the write filter can be defined by creating new datasets, since only the dataset zroot/ROOT/default is protected from write accesses; all other system datasets, including newly created datasets, are excluded from the protection.
This chapter shows an example of how a separate dataset can be created for the TwinCAT boot directory, thereby excluding this directory from the write filter protection.
Requirements:
- Save the TwinCAT boot directory in advance if you follow this example.
- Disable the write filter (see Enabling or disabling the write filter).
Proceed as follows:
- 1. Enter the command
doas rm -rf /usr/local/etc/TwinCAT/3.1/Boot/*. - 2. The directory
usr/local/etc/TwinCAT/3.1/Bootis detached from the file hierarchy. - 3. Enter the command
doas zfs create -o mountpoint=/usr/local/etc/TwinCAT/3.1/Boot zroot/usr/TwinCAT-Bootto mount the new datasetzroot/usr/TwinCAT-Boot.
- You have successfully created a new dataset for the TwinCAT boot directory. Use
zfs mountto display all mounted datasets, including the new datasetzroot/usr/TwinCAT-Boot. From now on, all directories below this directory are no longer protected from write access by an active write filter.