T_CP24Time2a

Three octets binary time format.

TYPE T_CP24Time2a :
STRUCT
    Milliseconds    : WORD; (* 0..59.999ms = 60sec = 1min *)
    IVResMinute     : BYTE; (* Bit 7 = IV (invalid time), Bit 6 = Res (spare bit), Bit 0..5 = Minutes (0..59min) *)
END_STRUCT
END_TYPE

Requirements

Development Environment

Target System

PLC libraries to include

TwinCAT v2.9.0 Build >= 1030

PC or CX (x86)

TcIEC870_5_101.Lib

( Standard.Lib; TcBase.Lib; TcSystem.Lib; TcUtilities.Lib;  are included automatically )

TwinCAT v2.10.0 Build >= 1301

CX (ARM)