GetValue / SetValue / RNtfValue

GetValue

GetValue / SetValue / RNtfValue 1:

The GetValue method is used to query the property of the OCA object. If the query was successful, the result is output in the property stSetting.

GetValue / SetValue / RNtfValue 2:

Cyclic method call

Since several PLC cycles may pass between sending and the response from the device, this method should be executed cyclically.

Syntax

VAR_INPUT
   pLink    : POINTER TO ST_Link;
   bExecute : BOOL;
END_VAR

GetValue / SetValue / RNtfValue 3: Inputs

Name

Type

Description

pLink

POINTER TO ST_Link

Pointer for establishing a connection between OCA objects and the OCA device

bExecute

BOOL

The method is executed with a positive edge at the bExecute input.

SetValue

GetValue / SetValue / RNtfValue 4:

The SetValue method can be used to set the property of an OCA object. If the method was executed successfully, the result is output in the property stSetting.

GetValue / SetValue / RNtfValue 5:

Cyclic method call

Since several PLC cycles may pass between sending and the response from the device, this method should be executed cyclically.

Syntax

VAR_INPUT
   pLink    : POINTER TO ST_Link;
   bExecute : BOOL;
   sValue   : STRING;
   eCmdMode : E_OcaMessageTypeCmd;
END_VAR

GetValue / SetValue / RNtfValue 6: Inputs

Name

Type

Description

pLink

POINTER TO ST_Link

Pointer for establishing a connection between OCA objects and the OCA device.

bExecute

BOOL

The method is executed with a positive edge at the bExecute input.

nSetting

UDINT

Value to be assigned to the property of the OCA object.

eCmdMode

OcaMessageTypeCmd

Depending on whether confirmation is required or not, this input variable is set to E_OcaMessageTypeCmd.OcaCmdRrq or E_OcaMessageTypeCmd.OcaCmd.

RNtfValue

GetValue / SetValue / RNtfValue 7:

If the OCA object was prompted to notify changes (using the Subscription method), incoming notifications are read using the RNtfValue method.

GetValue / SetValue / RNtfValue 8:

Cyclic method call

Since several PLC cycles may pass between sending and the response from the device, this method should be executed cyclically.

Syntax

VAR_INPUT
   pLink           : POINTER TO ST_Link;
   bEnable         : BOOL;
   nSubscribtionNo : UDINT;
END_VAR

GetValue / SetValue / RNtfValue 9: Inputs

Name

Type

Description

pLink

POINTER TO ST_Link

Pointer for establishing a connection between OCA objects and the OCA device.

bExecute

BOOL

The method is executed with a positive edge at the bExecute input.

nSubscribtionNo

UDINT

Unique number for localizing the respective subscription.