E_TcPfw_TempSensType

This enumeration defines identifiers for the supported types of temperature sensors. These identifiers are used in ST_TcPfw_TempMparamFromHmi_Itf.

Syntax

TYPE E_TcPfw_TempSensType:
(* last modification: 17.02.2011 *)
(
eTcPfwTempSensT_NoSensor,
eTcPfwTempSensT_TC_B,
eTcPfwTempSensT_TC_E,
eTcPfwTempSensT_TC_J,
eTcPfwTempSensT_TC_K,
eTcPfwTempSensT_TC_L,
eTcPfwTempSensT_TC_N,
eTcPfwTempSensT_TC_R,
eTcPfwTempSensT_TC_S,
eTcPfwTempSensT_TC_T,
eTcPfwTempSensT_TC_U,

eTcPfwTempSensT_PT_100:=100,
eTcPfwTempSensT_NI_100,
eTcPfwTempSensT_NI_120,
eTcPfwTempSensT_PT_200,
eTcPfwTempSensT_PT_500,
eTcPfwTempSensT_PT_1000,
eTcPfwTempSensT_NI_1000,

eTcPfwTempsT_Customized:=10000
);
END_TYPE

Values

Name

Description

eTcPfwTempSensT_NoSensor

This identifier appears in the configuration of unused temperature controller zones.

eTcPfwTempSensT_TC_B

Type B sensor: 600 °C to 1800 °C

eTcPfwTempSensT_TC_E

Type B sensor: -100 °C to 1000 °C

eTcPfwTempSensT_TC_J

Type B sensor: -100 °C to 1200 °C

eTcPfwTempSensT_TC_K

Type B sensor: -100 °C to 1370 °C

eTcPfwTempSensT_TC_L

Type B sensor: -25 °C to 900 °C

eTcPfwTempSensT_TC_N

Type B sensor: -100 °C to 1300 °C

eTcPfwTempSensT_TC_R

Type B sensor: 0 °C to 1700 °C

eTcPfwTempSensT_TC_S

Type B sensor: 0 °C to 1700 °C

eTcPfwTempSensT_TC_T

Type B sensor: -100 °C to 400 °C

eTcPfwTempSensT_TC_U

Type B sensor: -25 °C to 600 °C

eTcPfwTempSensT_PT_100

PT100 sensor: -200 °C to 850 °C

eTcPfwTempSensT_NI_100

NI100 sensor: -60 °C to 250 °C.

eTcPfwTempSensT_NI_120

NI120 sensor: -60 °C to 320 °C.

eTcPfwTempSensT_PT_200

PT200 sensor: -200 °C to 850 °C

eTcPfwTempSensT_PT_500

PT500 sensor: -200 °C to 850 °C

eTcPfwTempSensT_PT_1000

PT1000 sensor: -200 °C to 850 °C

eTcPfwTempSensT_NI_1000

NI1000 sensor: -60 °C to 250 °C

eTcPfwTempsT_Customized

These and all higher numerical values mark application-specific temperature sensors.