FB_MTP_DIntMon

FB_MTP_DIntMon 1:

The function block FB_MTP_DIntMon provides the integer input value V for manual operation (e.g. via OPC UA). This value V can be monitored for up to 6 limits.

Further properties

Name of the object

Object description

WQC

OSLevel

Value scaling

Limit value monitoring

Inheritance hierarchy

FB_MTP_DIntView

    FB_MTP_DIntMon

Implemented interfaces

I_MTP_DIntMon

FB_MTP_DIntMon 2: Inputs

Name

Type

Description

OPC UA access

TagName

STRING

Name of the interface

-

TagDescription

STRING

Description of the interface

-

WQC

BYTE

Worst Quality Code

Read

OSLevel

BYTE

Level must be defined for system. Value 0 is reserved for local operation.

Read/write

V

DINT

Value

Read

VUnit

INT

Unit of value

Read

VSclMin

DINT

Scale start for value display

Read

VSclMax

DINT

Scale end for value display

Read

VAHEn

BOOL

Monitor limit Alarm High:

1: Monitoring active

0: No monitoring

Read

VALEn

BOOL

Monitor limit Alarm Low:

1: Monitoring active

0: No monitoring

Read

VWHEn

BOOL

Monitor limit Warning High:

1: Monitoring active

0: No monitoring

Read

VWLEn

BOOL

Monitor limit Warning Low:

1: Monitoring active

0: No monitoring

Read

VTHEn

BOOL

Monitor limit Tolerance High:

1: Monitoring active

0: No monitoring

Read

VTLEn

BOOL

Monitor limit Tolerance Low:

1: Monitoring active

0: No monitoring

Read

FB_MTP_DIntMon 3: Outputs

Name

Type

Description

OPC UA access

VAHAct

BOOL

Alarm High limit exceeded.

Read

VALAct

BOOL

Alarm Low limit not reached.

Read

VWHAct

BOOL

Warning High limit exceeded.

Read

VWLAct

BOOL

Warning Low limit not reached.

Read

VTHAct

BOOL

Tolerance High limit exceeded.

Read

VTLAct

BOOL

Tolerance Low limit not reached.

Read

External variables

Name

Type

Description

OPC UA access

VAHLim

DINT

Alarm High limit

Read/write

VALLim

DINT

Alarm Low limit

Read/write

VWHLim

DINT

Warning High limit

Read/write

VWLLim

DINT

Warning Low limit

Read/write

VTHLim

DINT

Tolerance High limit

Read/write

VTLLim

DINT

Tolerance Low limit

Read/write