FB_MTP_AnaReportValue

The function block FB_MTP_AnaReportValue provides an analog input value VIn of a manual operation (e.g. via OPC UA) for the documentation (output V). This value is assigned to exactly one service. Within this service, it can be assigned to one or more procedures.
Freezing the value
The value V can be frozen via the higher-level service (see FB_MTP_ServiceControl). If the input value VIn changes more than once during this time, it is signaled at output MissedValue = TRUE.
Further properties
Implemented interfaces
Inputs
Name | Type | Description | OPC UA access |
|---|---|---|---|
TagName | STRING | Name of the interface | - |
TagDescription | STRING | Description of the interface | - |
WQC | BYTE | Worst Quality Code | Read |
VIn | REAL | Input value | - |
VSclMin | REAL | Scale start for value display | Read |
VSclMax | REAL | Scale end for value display | Read |
VUnit | INT | Unit of value | Read |
Outputs
Name | Type | Description | OPC UA access |
|---|---|---|---|
MissedValue | BOOL | Change of the input value 1: The input value 0: The input value | Read |
V | REAL | Value that is made available via OPC UA. | Read |