Operation Mode
In this library, a distinction is made between Operator and Automatic as sources for switching requests. The Operation Mode is a state machine for managing switching requests from these sources.
Access routes
Automatic switching requests are written by the internal PLC logic. The variable names are extended by the suffix *Aut.
Operator switching requests are made manually (e.g. via OPC UA). They are declared as external variables and cannot be written via the internal PLC logic. Operator switching requests, add the suffix *Op to the variable name.
States
The state machine has three states: Offline, Operator and Automatic. No new switching requests are processed in the Offline state. In the Operator state, *Op switching requests are processed and in the Automatic state, *Aut switching requests are processed.
The current state is displayed via the outputs StateOffAct, StateOpAct, and StateAutAct.
State change
A state change is carried out via switching requests from the internal PLC logic or via an operator (according to the Handshake procedure). The input StateChannel is set via the internal PLC logic and indicates which source can currently trigger a state change.
If more than one state change is requested at the same time (e.g., StateOpAut = TRUE and StateOffAut = TRUE), the requests are discarded and Operation Mode remains in its current state.

![]() | A direct transition from the state |
![]() | The |
Inputs
Name | Type | Description | OPC UA access |
|---|---|---|---|
StateChannel | BOOL | Selection of switching requests for the state machine: 1: 0: | Read |
StateOffAut | BOOL |
| Read |
StateOpAut | BOOL |
| Read |
StateAutAut | BOOL |
| Read |
Outputs
Name | Type | Description | OPC UA access |
|---|---|---|---|
StateOffAct | BOOL | 1: Current state is | Read |
StateOpAct | BOOL | 1: Current state is | Read |
StateAutAct | BOOL | 1: Current state is | Read |
External variables
Name | Type | Description | OPC UA access |
|---|---|---|---|
StateOffOp | BOOL |
0→1: 1→0: Request has been processed. | Read/write |
StateOpOp | BOOL |
0→1: 1→0: Request has been processed. | Read/write |
StateAutOp | BOOL |
0→1: 1→0: Request has been processed. | Read/write |
Methods
Name | Type | Description |
|---|---|---|
IsOffline | BOOL | Returns |
IsOperator | BOOL | Returns |
IsAutomatic | BOOL | Returns |
SetOffline | BOOL | Sets the state machine Returns |
SetOperator | BOOL | Sets the state machine Returns |
SetAutomatic | BOOL | Sets the state machine Returns |