ReactiveByVoltageLim
The parameters of the ReactiveByVoltageLim group are used to set the reactive power control with voltage limitation (see Reactive power control with voltage limiting function Q(Ulim)).
Name | Default | Min | Max | Unit | Data type |
|---|---|---|---|---|---|
ReactiveByVoltageLimEnable | FALSE | BOOL | |||
Enabling the reactive power control with voltage limiting function | |||||
| [[94.0, 33.0], [96.0, 0.0], [104.0, 0.0], [106.0, -33.0]] | % | ARRAY[1..4, 1..2] OF REAL | ||
Reactive power voltage limitation characteristic curve (V/Vnom, Q/Pnom) | |||||
| 0.0 | -50.0 | +50.0 | % | REAL |
Offset of the voltage limitation characteristic curve (QOffset/Pnom) | |||||