ReactiveCapability

The parameters of the ReactiveCapability group are used to set the reactive power capacity (see Active power-dependent reactive power capacity).

Name

Default

Min

Max

Unit

Data type

ReactiveCapabilityEnable

FALSE

BOOL

Activating the reactive power

ReactiveCapabilityUdExt

 

%

ARRAY[1..3, 1..2] OF REAL

Characteristic curve of the underexcited reactive power capability (P/Pnom, Q/Pnom)

ReactiveCapabilityOvExt

 

 

 

%

ARRAY[1..3, 1..2] OF REAL

Characteristic curve of the overexcited reactive power capability (P/Pnom, Q/Pnom)