STcPowerMeasurePhasor

The structures STcPowerMeasurePowerDiag and STcPowerMeasurePhasorValues contain the calculated phasors and are summarized in the STcPowerMeasurePhasorArea structure.

STcPowerMeasurePhasorComplexValues

The size of a phasor in different display forms.

Name

Data Type

Unit

Description

fRe

REAL

V/A

Real component of the phasor.

fIm

REAL

V/A

Imaginary part of the phasor.

fAmp

REAL

V/A

Amplitude of the phasor.

fPhi

REAL

°

Phase angle of the phasor.

STcPowerMeasurePhasorValues

Determined phasors for the individual phases and the symmetrical components.

Name

Data Type

Description

L1

STcPowerMeasurePhasorComplexValues

Phasors of phase L1.

L2

STcPowerMeasurePhasorComplexValues

Phasors of phase L2.

L3

STcPowerMeasurePhasorComplexValues

Phasors of phase L3.

PosSeq

STcPowerMeasurePhasorComplexValues

Phasors from the positive-sequence system.

NegSeq

STcPowerMeasurePhasorComplexValues

Phasors from the negative-sequence system.

ZeoSeq

STcPowerMeasurePhasorComplexValues

Phasors from the zero system.

STcPowerMeasurePhasorFrequency

The frequency and frequency change determined from the phasors.

Name

Data Type

Unit

Description

fF

REAL

Hz

Determined frequency.

fR

REAL

Hz/s

Determined frequency change.

STcPowerMeasurePhasorArea

Summary of the phasors.

Name

Data Type

Description

nTimestamp

DCTIME

Time of update.

Diag

STcPowerMeasurePowerDiag

State of determination.

Voltage

STcPowerMeasurePhasorValues

Phasors of the voltage.

Current

STcPowerMeasurePhasorValues

Phasors of the current.

Frequency

STcPowerMeasurePhasorFrequency

Determined frequency.