Addressing
In the Addressing tab, you can address the devices on the DALI lines or activate the Manual Mode. The selected DALI line is blocked for control and all connected devices are temporarily inactive. The state of the illumination freezes and the sensors do not provide any presences. During operation, it is recommended to first activate Manual Mode for individual areas to ensure that the lighting is switched on for safety's sake.
In Manual Mode, all lamps on all lines are addressed via a broadcast command. You can set the lamps directly to their maximum or minimum value. Alternatively you can dim directly to a certain value using the slider.
This mode is important, especially prior to the initial construction, so that the electricians can check and test their DALI wiring. If the individual lamps do not react here, this means that there is a defect in the ECG (electronic control gear), the lamp or the cabling.