Global lighting functions
In addition to the functions within the room, luminaires are controlled by higher-level application functions. These must be adapted to the requirements for the operation of the building and determined in the planning phase.
Possible global lighting functions can be:
- Burglary
A connection between the BA system and the burglary alarm system triggers a global command that switches on the illumination throughout the building.
The implementation of this lighting function can be found in the template FB_BA_BuildingLighting. - Fire
The illumination is switched on by a connection between the BA system and the fire alarm system.
The implementation of this lighting function can be found in the template FB_BA_BuildingLighting. - Maintenance mode
When maintenance mode is triggered via the management and operating device (MBE) or TwinCAT 3 HMI, illumination is switched on in a specific area of the building.
The implementation of this lighting function can be found in the template FB_BA_FloorLighting. - Night watchman tour.
The illumination is switched on and dimmed to a certain value during the security staff's tours.
Operation can be carried out via a time schedule or manually.
The implementation of this lighting function is located in the template FB_BA_FloorLighting.