Example

The following code shows how to use the dynamic creation/deletion feature.

Variables:

PROGRAM DYN_OBJECTS
VAR
    fbDynObject : FB_BACnet_DynObjectManager := (bCycleObjects := TRUE);

    bCreate : BOOL;
    bDelete : BOOL;

    DynView : POINTER TO FB_BACnet_View;
    DynAV01 : POINTER TO FB_BACnet_AV;
    DynBV01 : POINTER TO FB_BACnet_BV;
    nCounter : UDINT;
END_VAR

Code:

// Management FB has to be called in every cycle
fbDynObject();

IF (fbDynObject.Ready) THEN
    IF (bCreate) THEN
        bCreate := FALSE;
        // [Variant 1] Create standard object types:
        IF (fbDynObject.CreateObject(
                DynView,
                E_BACnet_CreateObjType.eStructuredView,
                BACnet_Globals.nBACnetInstId_Auto,
                'DynView',
                'Dynamic View',
                0))
        THEN
            // [Optional] set object properties...
        END_IF
        IF (fbDynObject.CreateObject(
                DynAV01,
                E_BACnet_CreateObjType.eAnalogValue,
                BACnet_Globals.nBACnetInstId_Auto,
                '\/DynAV01',
                '\/Dynamic AV 1',
                DynView))
        THEN
            // [Optional] set object properties...
            DynAV01^.eUnit := E_BA_Unit.eTemperature_DegreesCelsius;
        END_IF
        IF (fbDynObject.CreateObject(
                DynBV01,
                E_BACnet_CreateObjType.eBinaryValue,
                BACnet_Globals.nBACnetInstId_Auto,
                '\/DynBV01',
                '\/Dynamic BV 1',
                DynView))
        THEN
            // [Optional] set object properties...
            DynBV01^.sInactiveText := 'Off';
            DynBV01^.sActiveText := 'On';
        END_IF
    END_IF

    IF (bDelete) THEN
        bDelete := FALSE;
        // [Variant 1] Delete all objects conveniently via object manager:
        fbDynObject.Reset();

        // [Variant 2] Delete all objects manually:
         (*
        fbDynObject.DeleteObject(DynAV01);
        fbDynObject.DeleteObject(DynBV01);
        fbDynObject.DeleteObject(DynView);
        *)
    END_IF

    // Sample PLC code:
    // > Take care of valid object pointers!
    IF (fbDynObject.CreatedObjects > 0) THEN
        nCounter := (nCounter+1);
        // Simulate changing value:
        DynAV01^.bEnPgm := TRUE;
        DynAV01^.fValPgm := (TO_REAL(nCounter MOD 1000)/100);

        // [Variant 2] Call created objects manually
        IF (NOT fbDynObject.bCycleObjects) THEN
            DynView^();
            DynAV01^();
            DynBV01^();
        END_IF
    END_IF
END_IF