Limit_Enable

This property specifies two flags that enable and disable compliance with the upper alarm limit and lower alarm limit separately.

Limit_Enable 1:

Please note:
up to BACnet revision 12 there was an error in the description of the Property Description in the BACnet standard. Only event reporting was enabled / disabled up to version 12. As of revision 13, this specification was changed in the BACnet standard. Now, observation of these properties is enabled / disabled.