E_HVACReqPump

TYPE E_HVACReqPump:
(
    eHVACReqPump_No             := 0,
    eHVACReqPump_OT_LL          := 1,
    eHVACReqPump_OT_HL          := 2,
    eHVACReqPump_VP             := 3,
    eHVACReqPump_OT_LL_OR_VP    := 4,
    eHVACReqPump_OT_HL_OR_VP    := 5,
    eHVACReqPump_OT_LL_AND_VP   := 6,
    eHVACReqPump_OT_HL_AND_VP   := 7
END_TYPE

eHVACReqPump_No: There is no request on the part of the Enum to control the pump

eHVACReqPump_OT_LL: The outside temperature (OT = rOutsideTemp) must be smaller than rOutsideTempLowLimit (LL = Lower Limit)

eHVACReqPump_OT_HL: The outside temperature (OT = rOutsideTemp) must be larger than rOutsideTempHighLimit (HL = Higher Limit)

eHVACReqPump_VP: The valve position (VP = rValvePosition) must be larger than rValvePositionLimitOn

eHVACReqPump_OT_LL_OR_VP: The outside temperature (OT = rOutsideTemp) must be smaller than rOutsideTempLowLimit (LL = Lower Limit) OR the valve position (VP = rValvePosition) must be larger than rValvePositionLimitOn

eHVACReqPump_OT_HL_OR_VP: The outside temperature (OT = rOutsideTemp) must be larger than rOutsideTempHighLimit (HL = Higher Limit) OR the valve position (VP = rValvePosition) must be larger than rValvePositionLimitOn

eHVACReqPump_OT_LL_AND_VP: The outside temperature (OT = rOutsideTemp) must be smaller than rOutsideTempLowLimit (LL = Lower Limit) AND the valve position (VP = rValvePosition) must be larger than rValvePositionLimitOn

eHVACReqPump_OT_HL_AND_VP: The outside temperature (OT = rOutsideTemp) must be larger than rOutsideTempHighLimit (HL = Higher Limit) AND the valve position (VP = rValvePosition) must be larger than rValvePositionLimitOn