Vision Service doesn't start
Situation | The TwinCAT Vision Service doesn't start. This can be seen by the connection status "Offline" on the Service Configuration tab in the VISION node. |
Solution | If the TwinCAT Version Service only fails to start once or fails, it can be reactivated with a TwinCAT restart (click However, if it generally fails to start (after the system startup), the service must be re-registered as a TwinCAT service. To do this, follow these steps:
TwinCAT must be in Config mode so that the Vision service can be started. Therefore, the machine must be restarted if the Vision service is to be restarted. If the Vision service is to be manually stopped, you can use the command " |