Topics
The message broker manages the addressing of messages via so-called "Topics". A topic can be thought of as a hierarchically organized mailbox, where the individual hierarchical levels are separated from each other by a "/". Sample:
Campus/Building1/Floor2/Room3/TemperatureWhen a publisher sends a message, it always specifies for which topic it is intended. A subscriber indicates which topic it is interested in. The message broker forwards the message accordingly.

Wildcards
It is possible to use wildcards in conjunction with topics. A wildcard is used to represent part of the topic. In this case a subscriber may receive messages from several topics. A distinction is made between two types of wildcards:
- Single-level wildcards
- Multi-level wildcards
Example for single-level wildcard:
The + symbol describes a single-level wildcard. If it is used by the subscriber as described below, for example, corresponding messages to the topics are either received by the subscriber or not.
- The receiver subscribes to Campus/Building1/Floor2/+/Temperature
- The publisher sends to Campus/Building1/Floor2/Room1/Temperature - OK
- The publisher sends to Campus/Building1/Floor2/Room2/Temperature - OK
- The publisher sends to Campus/Building42/Floor1/Room1/Temperature - NOK
- The publisher sends to Campus/Building1/Floor2/Room1/Fridge/Temperature - NOK
Example for multi-level wildcard:
The # symbol describes a multi-level wildcard. If it is used by the subscriber as described below, for example, corresponding messages to the topics are either received by the subscriber or not. The # symbol must always be the last symbol in a topic string.
- The receiver subscribes to Campus/Building1/Floor2/#
- The publisher sends to Campus/Building1/Floor2/Room1/Temperature - OK
- The publisher sends to Campus/Building1/Floor2/Room2/Temperature - OK
- The publisher sends to Campus/Building42/Floor1/Room1/Temperature - NOK
- The publisher sends to Campus/Building1/Floor2/Room1/Fridge/Temperature - OK
- The publisher sends to Campus/Building1/Floor2/Room1/Humidity - OK