Activating the S7 protocol access
The following screenshots show a sample activation of the S7 protocol functions in the TIA portal, which is usually only necessary for S7-1200 and S7-1500 controllers. Please note that the screenshots differ from your operating environment and may look different depending on the TIA version.
- 1. Firstly activate the access via the access level.
- 2. Then activate the COTP PUT/GET access.
- 3. Disable the optimized block access.
Notice | |
Hardware Download Please note that you have to perform a hardware download after changing the access parameters so that these changes become active. |