Param_Acsi

Namespace: Tc3_Acsi
Type: Parameter list
Library: Tc3_Acsi (Tc3_Acsi.compiled-library)

Parameter

Name

Type

Value

Description

cMaxLengthOfObjectName

UDINT

64

Maximum length of the object name string.

cMaxLengthOfObjectReference

UDINT

255

Maximum length of the reference string.

cMaxLengthOfVisString64

UDINT

64

Maximum length of the “VisString64” data type.

cMaxLengthOfVisString129

UDINT

129

Maximum length of the “VisString129” data type.

cMaxLengthOfVisString255

UDINT

255

Maximum length of the “VisString255” data type.

cMaxLengthOfClassName

UDINT

20

Maximum name length of the logical node or CDC.

cMaxLengthOfQualityString

INT(18..19)

18

Maximum length of the “Quality” data type formatted as a string. When the value is 19, the optional parameter “Derived” is also included in the string.

 

 

 

 

cDefault_TimeStamp

T_UtcTime

secondSinceEpoch:=DT#1970-01-01-00:00:00, fractionOfSecond:=[0,0,0], quality:=(LeapSecondsKnown:=0, ClockFailure:=0, ClockNotSynchronized:=0, Accuracy0:=0, Accuracy1:=0, Accuracy2:=0, Accuracy3:=0, Accuracy4:=0)

Default initial value for all “TimeStamp” DA instances.

cDefault_EntryTime_D

DATE

D#1984-01-01

Default initial value for all "EntryTime.day" data element instances.

cDefault_EntryTime_TimeOfDay

TOD

TOD#0:0:0

Default initial value for all “EntryTime.TimeOfDay” data element instances.

cDefault_EntryTime

T_BinaryTime

timeOfDay:=cDefault_EntryTime_TimeOfDay, day:=0

Default initial value for all “EntryTime” DA instances.

cDefault_Currency

STRING(3)

''

Default initial value for all “Currency” DA instances.

cDefault_EntryID

T_OCTET8

[8(0)]

Default initial value for all “EntryID” DA instances.

cDefault_Originator

ST_AcsiOriginator

orCat:=E_AcsiOrCategory.NotSupported, orIdent:=[64(0)]

Default initial value for all “Originator” DA instances.

cDefault_Quality

ST_AcsiQuality

Validity0:=0, Validity1:=0, Overflow:=0, OutOfRange:=0, BadReference:=0, Oscillatory:=0, Failure:=0, OldData:=0, Inconsistent:=0, Inaccurate:=0, Source:=0, Test:=0, OperatorBlocked:=0

Default initial value for all “Quality” DA instances.

cDefault_Dbpos

E_AcsiDbpos

E_AcsiDbpos.Intermediate

Default initial value for all “Dbpos” DA instances.

cDefault_Tcmd

E_AcsiTcmd

E_AcsiTcmd.Stop

Default initial value for all “Tcmd” DA instances.

cDefault_BrCB_OptFlds

ST_AcsiOptionalFields

SequenceNumber:=TRUE, ReportTimeStamp:=TRUE, ReasonForInclusion:=TRUE, DataSetName:=TRUE, DataReference:=FALSE, BufferOverflow:=TRUE, EntryID:=TRUE, ConfRevision:=TRUE, Segmentation:=FALSE

Default initial value for all BRCB “OptionalFields” DA instances.

cDefault_BrCB_TrgOps

ST_AcsiTriggerConditions

DataChange:=FALSE, QualityChange:=FALSE, DataUpdate:=FALSE, Integrity:=FALSE, GeneralInterrogation:=TRUE

Default initial value for all BRCB “TriggerConditions” DA instances.

cDefault_BrCB_TimeOfEntry

T_BinaryTime

timeOfDay:=TOD#0:0:0, day:=0

Default initial value for all BRCB “TimeOfEntry” DA instances.

cDefault_UrCB_OptFlds

ST_AcsiOptionalFields

SequenceNumber:=TRUE, ReportTimeStamp:=TRUE, ReasonForInclusion:=TRUE, DataSetName:=TRUE, DataReference:=FALSE, BufferOverflow:=FALSE, EntryID:=FALSE, ConfRevision:=TRUE, Segmentation:=FALSE

Default initial value for all URCB “OptionFields” DA instances.

cDefault_UrCB_TrgOps

ST_AcsiTriggerConditions

DataChange:=FALSE, QualityChange:=FALSE, DataUpdate:=FALSE, Integrity:=FALSE, GeneralInterrogation:=TRUE

Default initial value for all URCB “TriggerConditions” DA instances.

cDefault_GoCB_MinTime

UDINT(1..16#7FFFFFFF)

50

Default GOCB delay time for sending the repetitions in milliseconds.

cDefault_GoCB_MaxTime

UDINT(1..16#7FFFFFFF)

5,000

Default GOCB monitoring time in milliseconds.

cDefault_GoCB_Multiplier

BYTE(1..BYTE#16#FF)

2

Default initial value for GOOSE publisher transmission repeat multiplier.

cDefault_GoCB_Security

DWORD(0..16#0FFFFFFF)

0

Default GOOSE header Reserved1 and Reserved2 28 security bits.

cDefault_LCB_OldEntrTm

T_BinaryTime

timeOfDay:=TOD#0:0:0, day:=0

Default initial value for all LCB “OldEntrTm”.

cDefault_LCB_NewEntrTm

T_BinaryTime

timeOfDay:=TOD#0:0:0, day:=0

Default initial value for all LCB “NewEntrTm”.

cDefault_LCB_OptFlds

ST_AcsiLogOptionalFields

ReasonForInclusion:=TRUE

Default initial value for all LCB “OptionFields” DA instances.

cDefault_LCB_TrgOps

ST_AcsiTriggerConditions

DataChange:=FALSE, QualityChange:=FALSE, DataUpdate:=FALSE, Integrity:=FALSE, GeneralInterrogation:=TRUE

Default initial value for all LCB “TriggerConditions” DA instances.

cDefault_MsvCB_OptFlds

ST_AcsiSvOptionalFields

SampleSynchronized:=TRUE

Default initial value for all MSVCB “OptionFields” DA instances.

cDefault_UsvCB_OptFlds

ST_AcsiSvOptionalFields

SampleSynchronized:=TRUE

Default initial value for all USVCB “OptionFields” DA instances.

cDefault_Per

E_AcsiPer

E_AcsiPer.Hourly

Default initial value for all “perRs” or “chrPerRs” DA instances.

cDefault_Acs

E_AcsiAcs

E_AcsiAcs.Low

Default initial value for all “sptAcs” DA instances.

 

 

 

 

cPresence_AnalogueValue

E_AcsiAnalogueValuePresCond

E_AcsiAnalogueValuePresCond.both_CO_f

Default presence of the “AnalogueValue” data elements: “i” and/or “f”.

In the status value “i” and “f” (both) are visible, in the control value only “f” is visible.

cPresence_Cell_xEnd

BOOL

FALSE

Default presence of “Cell.xEnd”.

cPresence_Cell_yStart

BOOL

FALSE

Default presence of “Cell.yStart”.

cPresence_Cell_yEnd

BOOL

FALSE

Default presence of “Cell.xEnd”.

cPresence_Point_zVal

BOOL

FALSE

Default presence of “Point.zVal”.

cPresence_RangeConfig_limDb

BOOL

FALSE

Default presence of “RangeConfig.limDb”.

cPresence_Unit_multiplier

BOOL

FALSE

Default presence of “Unit.multiplier”.

cPresence_ValWithTrans_transInd

BOOL

FALSE

Default presence of “ValWithTrans.transInd”.

cPresence_Vector_ang

BOOL

FALSE

Default presence of “Vector.ang”.

cPresence_Oper_AnalogueValue_operTm

BOOL

FALSE

Default presence of “Oper.ctlVal(AnalogueValue).operTm”

cPresence_Oper_BOOLEAN_operTm

BOOL

FALSE

Default presence of “Oper.ctlVal(BOOLEAN).operTm”

cPresence_Oper_CODEDENUM_operTm

BOOL

FALSE

Default presence of “Oper.ctlVal(CODEDENUM).operTm”

cPresence_Oper_ENUMERATED_operTm

BOOL

FALSE

Default presence of “Oper.ctlVal(ENUMERATED).operTm”

cPresence_Oper_INT32_operTm

BOOL

FALSE

Default presence of “Oper.ctlVal(INT32).operTm”

cPresence_Oper_INT8_operTm

BOOL

FALSE

Default presence of “Oper.ctlVal(INT8).operTm”

cPresence_SBOw_AnalogueValue_operTm

BOOL

FALSE

Default presence of “SBOw.ctlVal(AnalogueValue).operTm”

cPresence_SBOw_BOOLEAN_operTm

BOOL

FALSE

Default presence of “SBOw.ctlVal(BOOLEAN).operTm”

cPresence_SBOw_CODEDENUM_operTm

BOOL

FALSE

Default presence of “SBOw.ctlVal(CODEDENUM).operTm”

cPresence_SBOw_ENUMERATED_operTm

BOOL

FALSE

Default presence of “SBOw.ctlVal(ENUMERATED).operTm”

cPresence_SBOw_INT32_operTm

BOOL

FALSE

Default presence of “SBOw.ctlVal(INT32).operTm”

cPresence_SBOw_INT8_operTm

BOOL

FALSE

Default presence of “SBOw.ctlVal(INT8).operTm”

cPresence_Cancel_AnalogueValue_operTm

BOOL

FALSE

Default presence of “Cancel.ctlVal(AnalogueValue).operTm”

cPresence_Cancel_BOOLEAN_operTm

BOOL

FALSE

Default presence of “Cancel.ctlVal(BOOLEAN).operTm”

cPresence_Cancel_CODEDENUM_operTm

BOOL

FALSE

Default presence of “Cancel.ctlVal(CODEDENUM).operTm”

cPresence_Cancel_ENUMERATED_operTm

BOOL

FALSE

Default presence of “Cancel.ctlVal(ENUMERATED).operTm”

cPresence_Cancel_INT32_operTm

BOOL

FALSE

Default presence of “Cancel.ctlVal(INT32).operTm”

cPresence_Cancel_INT8_operTm

BOOL

FALSE

Default presence of “Cancel.ctlVal(INT8).operTm”

cPresence_BrCB_ResvTms

BOOL

FALSE

Default presence of “BRCB.ResvTms”

cPresence_BrCB_Owner

BOOL

FALSE

Default presence of “BRCB.Owner”

cPresence_UrCB_Owner

BOOL

FALSE

Default presence of “URCB.Owner”

cPresence_LCB_OptFlds

BOOL

FALSE

Default presence of “LCB.OptFlds”

cPresence_LCB_BufTm

BOOL

FALSE

Default presence of “LCB.BufTm”

cPresence_GoCB_MinTime

BOOL

FALSE

Default presence of “GOCB.MinTime”

cPresence_GoCB_MaxTime

BOOL

FALSE

Default presence of “GOCB.MaxTime”

cPresence_GoCB_FixedOffs

BOOL

FALSE

Default presence of “GOCB.FixedOffs”