AcsiOriginator
Initializes the data elements of the structure: ST_AcsiOriginator.
Namespace: Tc3_Acsi
Library: Tc3_Acsi (Tc3_Acsi.compiled-library)
FUNCTION AcsiOriginator : ST_AcsiOriginator
VAR_INPUT
orCat : E_AcsiOrCategory;
orIdent : T_OCTET64;
END_VAR
Inputs
Name | Type | Description |
|---|---|---|
orCat | Data element "orCat" to be set. | |
orIdent | Data element "orIdent" to be set. |
Return value
Name | Type | Description |
|---|---|---|
AcsiOriginator | Structure with initialized data elements. |
Example
METHOD FINAL Sample_AcsiOriginator : BOOL
VAR
org: ST_AcsiOriginator;
orIdent : T_OCTET64:=[16#36,16#31, 16#38, 16#35, 16#30];
END_VARorg:=AcsiOriginator(orCat:=E_AcsiOrCategory.StationControl, orIdent:=orIdent);
Sample_AcsiOriginator:=TRUE;