FB_GetDBXMLConfig

FB_GetDBXMLConfig 1:

The FB_GetDBXMLConfig function block can be used to read all databases that are declared in the XML configuration file.

VAR_INPUT

VAR_INPUT
    sNetID   : T_AmsNetId;
    cbDBCfg  : UDINT;
    pDBCfg   : POINTER TO ARRAY [0.. MAX_XML_DECLARATIONS] OF ST_DBXMLCfg;
    bExecute : BOOL;
    tTimeout : TIME;
END_VAR

sNetID: String containing the AMS network ID of the target device, at which the ADS command is directed.

cbDBCfg: Indicates the length of the array, into which the configurations are to be written.

pDBCfg: Indicates the pointer address of the array, into which the configurations are to be written.

bExecute: The command is executed with a rising edge.

tTimeout: Indicates the time before the function is cancelled.

VAR_OUTPUT

VAR_OUTPUT
    bBusy  : BOOL;
    bError : BOOL;
    nErrID : UDINT;
END_VAR

bBusy: The command is in the process of being transmitted by ADS. No new command will be accepted as long as bBusy remains TRUE.

bError: Becomes TRUE, as soon as an error occurs.

nErrID: Returns the ADS error code if the bError output is set.

Requirements

Development environment

Target platform

PLC libraries to be linked

TwinCAT v3.0.0

PC or CX (x86)

Tc2_Database