EL6631 – LEDs

LEDs for EtherCAT diagnosis
|
LED |
Display |
Description | |
|---|---|---|---|
|
RUN |
green |
off |
State of the EtherCAT State Machine: |
|
flashing |
State of the EtherCAT State Machine: | ||
|
off (1 s) |
State of the EtherCAT State Machine: | ||
|
on |
State of the EtherCAT State Machine: | ||
LED diagnosis PROFINET RUN/Err
|
Color green |
Color red |
Meaning |
|---|---|---|
|
off |
flashing |
Terminal starts |
|
flashing |
off |
No name |
|
1 s off, 200 ms on |
off |
No IP address |
|
on |
off |
EL terminal is parameterized |
LED diagnosis PROFINET Err
|
Colours green |
Colours red |
Meaning |
|---|---|---|
|
off |
flashing |
no AR established with any device |
|
off |
1 s off, 200 ms on |
At least one device has not established an AR |
|
1 s off, 200 ms on |
off |
At least one device has signaled an error, e.g. that there is a module difference or that the error bit for an IO-CR is set (Problem Indicator) |
|
flashing |
off |
At least one device is signaling that its status is ‘Stop’ (Provider State Stop) |
|
on |
off |
All PROFINET devices are in data exchange mode |
If there are several different errors, then the error that is located at the top of (or higher in) the table is always displayed.
LEDs starting up
|
Run |
PN Run/Err |
PN Err |
Meaning |
|---|---|---|---|
|
off |
off |
off |
No electrical voltage connected to E-bus. The EL6631 must be exchanged if EtherCAT terminals behind it function. |
|
off |
off |
red on |
EL terminal is starting up; after approx. 10 seconds, the LED should go out. If this does not happen, the EL6631 module must be exchanged. |