EL6631-0010 – LEDs

LEDs for EtherCAT diagnosis
LED |
Display |
Description | |
---|---|---|---|
RUN |
green |
off |
State of the EtherCAT State Machine: |
flashing |
State of the EtherCAT State Machine: | ||
off (1 s) |
State of the EtherCAT State Machine: | ||
on |
State of the EtherCAT State Machine: |
LED diagnosis PROFINET RUN/Err
Colors green |
Colors red |
Meaning |
---|---|---|
on |
off |
EL terminal is parameterized |
off (1 s) |
off |
EL6631-0010 does not have an IP address |
flashing |
off |
EL6631-0010 still has not received a PROFINET name |
off |
flashing |
Terminal starts |
LED diagnosis PROFINET Err
Colors green |
Colors red |
Meaning |
---|---|---|
on |
off |
EL terminal is exchanging data |
flashing |
off |
EL terminal is exchanging data, but the provider status is stopped |
off (1 s) |
off |
EL terminal is exchanging data, but the modules are different |
off |
flashing |
No AR established, |
flashing |
flashing |
Identify EL terminal through PROFINET "flashing" |
LEDs starting up
Run |
PN Run/Err |
PN Err |
Meaning |
---|---|---|---|
off |
off |
off |
No electrical voltage connected to E-bus. The EL6631-0010 must be exchanged if EtherCAT terminals behind it need to function. |
off |
off |
red on |
EL terminal is starting up; after approx. 10 seconds, the LED should go out. If this does not happen, the EL6631-0010 module must be exchanged. |