Init Parameter

General

Homing Position

Name

Default value

Unit

Type

Homing Position

0.0

[PosUnit]

LREAL

The parameter Homing Position defines the absolute reference position. The axis is set to this position after a successful homing procedure. This parameter has an effect when the value #Default is used for the reference position input in the command to start a homing procedure (e.g., MC_Home).

Sequence

A homing process has several phases. The following parameters can be used to enable and configure individual phases.

Move to Cam Enabled

Name

Default value

Unit

Type

Move to Cam Enabled

FALSE

 

BOOL

 

Move to Cam Distance

10.0

[PosUnit]

LREAL

 

Move to Cam Velocity

30.0

[PosUnit]/s

LREAL

Enabling the Move To Cam Enabled parameter (value: TRUE) adds a sequence in the form of an axis movement to the initialization process. The system is searching for a reference signal. The axis continues to move until a corresponding value is detected at the input Signal. The logic of the input depends on the Invert Input parameter.

Move from Cam Enabled

Name

Default value

Unit

Type

Move from Cam Enabled

FALSE

 

BOOL

 

Move from Cam Distance

-10.0

[PosUnit]

LINT

 

Move from Cam Velocity

30.0

[PosUnit]/s

LINT

Enabling the Move From Cam Enabled parameter (value: TRUE) adds a sequence in the form of an axis movement to the initialization process. The axis continues to move until the reference signal at the Signal input returns to its inactive state. The logic of the input Signal depends on the Invert Input parameter.

Move to Sync Enabled

Name

Default value

Unit

Type

Move to Sync Enabled

FALSE

 

BOOL

 

Move to Sync Distance

10.0

[PosUnit]

LREAL

 

Move to Sync Velocity

30.0

[PosUnit]/s

LREAL

 

Move to Sync Source

ZeroImpulseCoE

 

MC.EHomingSyncSource

 

Move to Sync Edge

Positive

 

MC.ETouchProbeTriggerSource

Enabling the Move To Sync Enabled parameter (value: TRUE) adds a sequence in the form of an axis movement to the initialization process. The axis continues to move until a configured event is detected in touch probe unit 1 of the drive. The touch probe unit can be activated for the homing process using the parameter Move To Sync Source. In the cyclic interface (Data Area tab) between the axis or the subordinate drive object and the I/O device, the touch probe unit must be added and linked (it is recommended to configure the touch probe unit using Drive Manager 2).

Move to Initial Position Enabled

Name

Default value

Unit

Type

Move to Initial Position Enabled

FALSE

 

BOOL

 

Move to Initial Position

10.0

[PosUnit]

LREAL

 

Move to Initial Position Velocity

30.0

[PosUnit]/s

LREAL

Optionally, a homing process can be completed with a movement to an absolute target position if the parameter Move To Initial Point Enabled is set to TRUE.

Init Parameter 1:

View of subordinate objects

Depending on the Show Hidden Children setting in the context menu of an overlying parent object, child objects are hidden. Parameters and data areas of the child object are visible in the parent object when this setting is disabled.

  • To display child objects, right-click the parent object (context menu) > and click Show Hidden Children.

The following parameters originate from the nested Touch Probe object.

Binary Touch Probe

Name

Default value

Unit

Type

Input Inverted

FALSE

 

BOOL

Invert Input

If the value of the Input Inverted parameter is set to TRUE, the MC's internal algorithm inverts the logic of the input Signal for evaluation by the touch probe unit.