Etalon Exchange Format
Description
Etalon AG® is a vendor of hardware and software for the ISO-compliant measurement of machine tools. Measurement returns a set of parameter files in the proprietary exchange format. This format is similar to the format of Microsoft Windows INI files.
Row comments start by a double slash "//".
Notice | |
Etalon offers output in the exchange format in two variants: "Vendor" or "Kinematic". The "Vendor" variant must always be selected here. |
Programming Example
Position errors
// Every parameter is specified in a block.
// The block begins with the name of the parameter in square brackets.
[C0B]
VALUE = 0.000022355737
[A0B]
VALUE = 0.000047622950
Programming Example
// Lookup tables are specified via a 2D array called "Gridpoints".
[EXY]
Gridpoints = {
-280.0 -0.001358635132
-270.0 -0.000240680764
-260.0 0.000877273605
… // Further records in the form of "Parameter argument"
260.0 -0.001297146744
270.0 -0.000316265101
} // end of EXY