KIN_TYP_37 – Delta robot kinematics

The strut kinematics referred to as delta robot consists of 3 rotary axes arranged at an offset of 120 degrees guiding 2 parallel struts via connecting levers. In turn, these struts guide the tool platform. Tool orientation is constant.

Axis configuration in the NC channel

Axis identifier

X, Y, Z (J1, J2, J3)

Axis index

0, 1, 2

Kinematic structure

 

Tool axes

Workpiece axes

NC axes

X, Y, Z

-

KIN_TYP_37 – Delta robot kinematics 1:
Overhead delta robot kinematics
KIN_TYP_37 – Delta robot kinematics 2:
Offsets of delta robot kinematics

Offset data of kinematics

HD offset

param[i]

Description

Unit

HD1

0

Tool offset Z

1.0 E-4 mm

HD2

1

n.a.

[ - ]

HD3

2

n.a.

[ - ]

HD4

3

Radius of connecting line of bottom joint fixed points

1.0 E-4 mm

HD5

4

Radius of connecting line of top joint fixed points

1.0 E-4 mm

HD6

5

Bottom strut/arm length

1.0 E-4 mm

HD7

6

Top strut/arm length (connecting lever)

1.0 E-4 mm

HD8

7

Angular offset zero position J1 (ideal zero position of top arm horizontal)

1.0 E-4°

HD9

8

Angular offset zero position J2 (ideal zero position of top arm horizontal)

1.0 E-4°

HD10

9

Angular offset zero position J3 (ideal zero position of top arm horizontal)

1.0 E-4°

HD11

10

Limit of minimum joint angle J1 to J3

1.0 E-4°

HD12

11

Limit of maximum joint angle J1 to J3

1.0 E-4°

HD13

12

Z zero offset Cart. Workpiece coordinate system

1.0 E-4 mm

The Cartesian coordinate system lies in the origin of the motor mount. The parameter HD11 can shift the system origin so that it is located below the motor mount and the tool holder platform.

By default, the strut connecting levers must be horizontal in the drive zero position. If this is not the case, the angle zero position can be corrected for the internal kinematic model by the parameters HD8, HD9 and HD10. When all rotary axes move in positive rotation, the TCP moves in negative Z direction.

Example: Connecting lever in horizontal position, drive position: 900000 [ 1.0 E-4° ]

HD8, HD9, HD10: 900000 [ 1.0 E-4° ]

This kinematic transformation was developed in collaboration with Esslingen University (www.hs-esslingen.de).