Parameters

The touch probe must be configured in addition to supplying the input parameters described here. For more information on this function, see the section Configuration file.

The (calibrated) parameters of the touch probe (radius, length and offset in X and Y directions) are specified via the tool parameters.

Required parameters

Cycle parameters

Description

@P6

Measurement path in the direction of the (co-rotated) negative Z axis

@P87

Estimated diameter of the calibration sphere. Here, an approximate parameter is sufficient. For calculating measurement movements.

@P89

Index of the measured rotary axis (-1 with manual axis).

@P91

Expected X value of measured rotary axis. Here, an approximate parameter is sufficient. For calculating measurement movements.

@P92

Expected Y value of measured rotary axis. Here, an approximate parameter is sufficient. For calculating measurement movements.

@P93

Expected Z value of measured rotary axis. Here, an approximate parameter is sufficient. For calculating measurement movements.

Optional parameters

Cycle parameters

Description

@P13

Safety clearance to sphere during measurement movement

Default value = diameter of touch probe

@P14

Probe angle for first sphere measurement [degrees]. Refers to the (co-rotated) X axis.

Default value = 0

@P15

Probe angle difference between the co-rotated horizontal measurements for all measurements. [degrees]

Default value = 90

@P33

Crossover range during measurement process for all measurements

Additional motion path that exceeds the expected workpiece edge/workpiece surface

Default value = @P87/4

@P50

Filename including file suffix to write the output variables. If this is not transferred, only the output variables in the NC program are written, as usual.

Default value = "”

@P64

Definition of the section for sphere measurement for all measurements.

0: linear (default value)

1: circular (Caution: collision detection disabled)

@P90

Pre-positioning mode between sphere measurements

0: automatic by NC subroutines

1: manual or in manual mode (default value)

@P94

X value of rotary axis to define the inclined position of the touch probe at cycle start.

Default value = 0

@P95

Y value of rotary axis to define the inclined position of the touch probe head at cycle start.

Default value = 0

@P96

Z value of rotary axis to define the inclined position of the touch probe head at cycle start.

Default value = 0

@P97

Rotation angle to define the inclined position of the touch probe head at cycle start. [degrees]

Default value = 0

@P98

Probe angle for second sphere measurement. Refers to the (co-rotated) X axis. [degrees]

Default value = 0

@P99

Probe angle for third sphere measurement. Refers to the (co-rotated) X axis. [degrees]

Default value = 0

@P100

Angle travelled between measurement 1 and 2 of the measured rotary axis with manual pre-positioning. Here, an approximate parameter is sufficient. For calculating measurement movements. [degrees]

Default value = 0

@P101

Angle travelled between measurement 2 and 3 of the measured rotary axis with manual pre-positioning. Here, an approximate parameter is sufficient. For calculating measurement movements. [degrees]

Default value = 0

Notice

Disabled collision detection when @P64 is active.

If circular approach of the pre-position was selected in @P64, collision detection is disabled. This option may only be enabled if safe approach to the pre-position is ensured.

It is recommended to use the Syntax check to verify whether the input parameters are correctly assigned.

Logging

The logging function is enabled for this cycle.