Process (internal cycle)

Starting position before the cycle is called: The touch probe must be positioned at the start point manually or in automatic mode so that the probe can reach all points without collision.

The internal cycle process can be described as follows:

  1. The touch probe approaches the first pre-position specified in @P17 and @P18 relative to the start point.
  2. Measurement in Z direction
  3. The touch probe approaches the second pre-position in X direction specified in @P41 relative to the first measuring point.
  4. Measurement in Z direction
  5. The touch probe approaches the third pre-position specified in @P42 and @P44 relative to the start point.
  6. Measurement in Z direction
  7. If a retraction height was transferred, the touch probe is retracted to this height
Process (internal cycle) 1:
Align plane