Feedforward control (G135/G136/G137)
Syntax: | ||
G135 | Selecting feedforward control | modal |
G136 <axis_name>.. { <axis_name>.. } | Specify weighting | modal |
G137 | Deselecting feedforward control | modal, initial state |
Path distortions can be reduced by using velocity and acceleration feedforward control.
Axis group.specific activation is programmed with G135. An axis-specific percentage weighting of the calculated feedforward control variables in [%] takes place with G136. It is limited to 100% for all axes.
G137 deactivates axis group-specific feedforward control. In case of axes for which no feedforward control is to be implemented after global selection with G135, a percentage weighting of 0% must be specified with G136. It is also possible to enter the selection and weighting of feedforward control in a single block.
At every program start, feedforward control is explicitly disabled in the interpolator and the weighting factors are set to 100%.
If feedforward control is disabled or enabled during the NC program, the weighting factors remain at the values set by G136 or, if no G136 is programmed, to 100%.
Notice | |
After an axis exchange, the G136 weighting factors are reset to 100% for all axes involved. |
Programming Example
Feedforward control (G135/G136/G137)