Estimation of contour deviation

Contour deviations caused by the use of FIR axis filters are influenced by 3 factors, provided identical filters are used in every axis of an axis group:

  1. Cycle time
  2. Filter order
  3. Traverse feed rate

The following simple ratios apply:

The graphic below is generated for a cycle time of 1ms and an F1000 feed rate at a 90° corner using a moving average filter. With different marginal data, the filter orders must be uprated according to the ratios above.

Estimation of contour deviation 1:
Contour error per filter order at a 90° corner