Output of user-defined error messages to HMI
The output of user-defined error messages via the #ERROR command can be displaced on the GUI of the TwinCAT3 system. The range for possible error IDs is 1 – 1000.
Error texts can be saved in multiple languages.
![]() | The the errors texts specified in the P-STUP-00169 file are not linked to the output to the HMI. The required error texts must be integrated in both files. |
Error texts for output to HMI must be integrated in the
C:\TwinCAT\3.1\Target\Resource\TcCncUserEvents.xml
file.
Example
Integrating a message in TcCncUserEvents.xml

As an example, the error with ID 455 is integrated in the file:

![]() | With TwinCAT Build 4022.23 and higher, the configuration must be re-activated after integrating a user-defined error text.
|