Limits
The parameters listed below describe dynamic limits of an NC axis. They act as upper or lower limits for further parameters which can also be changed in the NC program to some extent.
Therefore, when the acceleration and ramp time values described in the following sections are weighted with the G functions G130 - G133 PROG, the minimum permissible ramp time cannot be undershot and the maximum permissible acceleration cannot be overshot.
- Maximum permissible axis acceleration (P-AXIS-00008)
- Minimum permissible ramp time (P-AXIS-00201)
- Maximum permissible axis velocity (P-AXIS-00212)
![]() | Note the following with regard to the maximum axis velocity P-AXIS-00212: |
- For G01 or G00 motions, this value represents the upper limit that can be reached by programming the F word or G00.
- With translatory or rotary axes (no spindles), it can be assumed that the resolution limits of the measuring system are taken into account in the setting.
- With spindle axes, the limit velocity for the measurement system P-AXIS-00220 is set as the maximum axis velocity.