ID 13449
The index of rotary axis to be measured is not defined @P89. | |||
Description | The index of the rotary axis to be measured was not defined. The axis index defines the location of the axis inside the axis group of the NC channel. Integers in the range [0… maximum number of axes -1] and the value -1 for manual axes are permitted. | ||
Response | Class | - | Error: Transition to error state. Complete reset of the NC channel necessary. |
Solution | Class | - | Define a valid value for the axis index with the parameter @P89. |
Error type | 1, Error message from the NC program | ||
| |||